What is the leading ignition protection type for UHP pressure transducers?

The leading ignition protection type is crucial for the electrical connection of a pressure sensor with explosion protection. It generally does not necessarily need to be the one with the stricter requirements. This applies, for instance, for the UHP pressure transducers of the WU series from WIKA. They are designed for use in semiconductor production.
Explosion protection can be an indispensable safety precaution there. This is due to the substances required for manufacturing include highly flammable gases. Consequently, you will find a threat of an explosive atmosphere forming.
Explosion protection concept
UHP pressure transducers for such processes should be designed with the corresponding safety. In addition to their small design and specific process connections, the models WUC-1x and WU-2x have a comprehensive explosion protection concept. The marking of the instruments provides info on this:
II 3G Ex ec ic IIC T6/T5/T4 Gc X
The abbreviations listed inside them mean, in more detail:
II 3G:
Equipment group 2 (all areas except mining), may be used in zone 2 (rare and short-term Ex atmosphere).
Ex ec ic:
Ignition protection types ?ec? (increased safety) and ?ic? (intrinsically Excellent ).
?Ex ec? has replaced the ignition protection type ?Ex nA? (non-sparking) since the start of 2022. However, this will not affect the Ex idea of the instruments.
IIC:
Explosion group (here: gases, resistive ignition energy of 40 �J, suitable for hydrogen/acetylene).
T6/T5/T4:
Temperature classes. T6 because the highest requirement stands for a maximum permissible surface temperature in the Ex environment < 85 �C (max. surface temperature of the WUC-1x and WU-2x: 40 �C).
Gc:
?Equipment Protection Level? (EPL) for zone 2 per IEC 60079-0
X:
Specific requirements which are listed in the operating instructions (for instance, the best mating connector).
?ec? is the leading ignition protection type
It is noticeable that the marking contains two ignition protection types. However, only 1 is pertinent for the electrical connection: the leading ignition protection type. Regarding the pressure transducers from the WU series, this can be the Ex ec (Ex nA around 2022) mentioned first and not the stricter Ex ic. This may also be seen in the connection values in the data sheet and operating instructions. Only the specification of the utmost supply voltage UN = 30 V, that is also stated in the IECEx certificate, is relevant here.
What does the classification ?Ex ic? are a symbol of? It only pertains to the potentiometer of the transducer. The resistive component has an intrinsically safe circuit and may therefore be adjusted to correct zero drift during operation. In their overall form, the WU models do not require an intrinsically safe circuit. However, they must never be disconnected from the circuit during operation or when an Ex atmosphere exists.
Note
More info on the WUC-1x and WU-2x UHP pressure transducers and on the subject of hydrogen are available on the WIKA website. Assuming you have any questions, your contact will gladly assist you to.